In AC induction motor when we start it, at starting it will take 5-7 times of motor rated current and it should come down in 4-5 second and will take no load current 40% - 50% of motor rated current.
Then we can now give it on load.
Now suppose if there is jam in mechanical coupling side, motor shaft then what would happen.
In this case if we start the motor then it take it's starting current 5-6 times of rated current and because it is jam either from mechanical coupling,gearbox or motor shaft problem
Motor can't start rotating and motor will take current 5-6 times and will not come down to it no load current as the delay time of EOCR end it will trip in stall fault.
So if it trip in stall fault then it is mechanically stuck up, it happens at start.
If motor trip in unbalance current:-
If 3 phase Induction motor was in running condition and trip during running in unbalance current.
Probable cause may be :-
1. Winding resistance unbalance.
2. Winding inductance unbalance.
3. Motor shaft play.
4. Motor vibration may increase.
5. Motor power cable burn somewhere/ carbonized.
May be other cause too.
1. First this is check the motor resistance and inductance by motor checker.
Procedure to check the motor Resistance:-
Disconnect all three motor phase connection from motor terminal , and take out the three lead from stud.
Then take reading of resistance of R- phase,Y- phase, B -phase by connecting checker lead to motor phase lead one by one.
Resistance should be balance.
Procedure to check the motor inductance:-
Disconnect all three motor phase connection from motor terminal , and take out the three lead from stud.
Then take reading of inductance of R- phase,Y- phase, B -phase by connecting checker lead to motor phase lead one by one.
Inductance should be balance.
2. In some cases i found if there is play in shaft then also motor trip in current unbalance. So if motor winding resistance and inductance is balance then check there also.
3. Check motor vibration also as per standard.
4. If motor power burn near socket, somewhere then also I found motor trip in unbalance.
So if motor trip in unbalance then above steps will help to find out the reason of motor trip.
If any queries then do comment.
Regards.